Unshielded
LUTZE SILFLEX® N Control Cable PVC
For Stationary Applications
Logo
Logo





Identification
Type
SI N TRAY-ER 25×AWG18 GR
Part No.
A3081825
Product status
Series
Use/Application/Properties
Application
- Machine tools, machine and plant construction, VAC technology as well as other uses.
- Compliant with NFPA 79 requirements
- TC-ER-JP for use with cable trays without conduit, which can reduce installation costs in industrial environments
- WTTC – wind turbine tray cable rating for use in wind power generation
- PLTC-ER Power Limited Tray Cable – Exposed Run
- ITC-ER Instrumentation Tray Cable – Exposed Run
- Dry, damp or wet locations
Properties
- Crush impact resistant
- Gas/vapor-tight sheath per UL 1277
- Non-wicking fillers
- Ecolab certified resistance to common cleaning agents and chemicals used in food and beverage washdown procedures
- Sunlight resistant
- Flame retardant
- "direct burial" for installation in the ground
- Talc free and silicone free
Technical Data
Construction
Description
SILFLEX® CONTROL CABLE PVC
Number of conductors/cross-section
25×AWG18
Number of conductors
25
Cross-section, metric
1 mm²
Cross-section AWG
AWG 18
Jacket material
PVC
Jacket color
grey similar to RAL 7001
Outer Ø
17.2 mm
Outer Ø
0.677 inch
Weight
46.7 kg/100 m
Weight
314 Lbs/Mft
Cu Index
22.5 kg/100 m
Cu Index
151 Lbs/Mft
Element 1
Element construction
AWG18/25C
Conductor construction
AWG 18 (19/30)
Conductor
- AWG conductor
- CU-wire bare
Conductor category
- Fine wire
- Class K
Conductor marking
black • with white number print • Ground conductor: green/yellow
Conductor insulation
- PVC/Nylon
- THHN – THWN
overall construction
Jacket characteristics
- Oil resistant
- Silicone free
Technical data
Rated voltage UN
- 600 V 90C UL TC-ER-JP
- 1000 V WTTC 90C
- 600 V UL MTW
- 1000 V 105C AWM
Temperature range fixed
-40 °C … +105 °C
Minimum bending radius fixed
4×cable OD
Element 1
Element construction
AWG18/25C
Approvals/Standards
Approvals
- UL Type MTW or DP-1
- Meets NEC 336, 392, 725, 727
- Class I and II, Div. 2 and Class I
- Zone 2 per NEC 501, 502, 505
- C(UL) TC and CIC FT4
- UL 1277
- TC-ER-JP
- WTTC
- PLTC-ER
- ITC-ER
UL style
AWM 20886
Conformity
- CE
- RoHS
- REACH
- TSCA
Oil resistant according to
Oil Res II
General
Note
CE These products are in conformity with the EU Low Voltage Directive 2014/35/EU